Section 2: UL Requirements
1. The RINGBACK @ CLOSE option must be selected for all commercial burglary applica-
tions.
2. The audible alarm must be placed where it can be heard by all partitions. A fire audible
alarm device shall be installed indoors in accordance with NFPA 74 and 72 Proprietary
Protective Signaling Systems. This may result in separate audible alarms, for fire and bur-
glary alarm signals.
NOTE An indoor/outdoor signaling device can be used if it gives different signals for fire and bur-
glary alarms.
3. For commercial burglary alarm units, the audible device must be installed where the audi-
ble test (BELL TEST @ ARM) can be heard by all system users in all partitions. If off
premises transmissions are used, the audible device can be installed inside the protected
premises.
4. For commercial burglary alarm units, the control panel and the audible device power sup-
ply must be protected by a 24 hour tamper switch and a lined housing, or they must be
enclosed in a protected area that is armed 24 hours a day. The tamper switches or pro-
tected area must be programmed as “not bypassable.”
5. For UL approved installations, the Regency Supervised Siren Module must be wired to the
4724. To warn of a fire, the module provides a UL temporal-three siren that uses three dis-
tinctive, repeating short beeps. The module converts the panel’s non-supervised, steady
fire cadence to a supervised, temporal-three fire cadence. This module also provides a dis-
tinctive supervised burglary (police) siren. See Figure 1 for details on wiring the module
to the 4724. For additional information, see the Regency Supervised Siren Module Instal-
lation Instructions (P/N 466-1584).
6. The 4724 is intended to be used for coverage under one management, one ownership, and
one address divided into separately armed, partitions (zones) of coverage.
Figure 1: Connecting the Supervised Siren Module to the 4724
8457G30B.DSF
FIRE
4.7k Ohm
EOL RESISTOR 49-365
(LOCATE AT SIREN)
1
COM
2
4
BURG
3
5
NO
7
C
6
COM
9
NC
8
+12V
10
SIREN
+
SIREN
--
+–
12V
SIREN/SOUNDER**
ZONE
LOOP
PWR
GND
ZONE
16*
INPUT
+12V
GND
13
P3
4.7K OHM EOL RESISTOR
600-7630
(LOCATE AT
SUPERVISED SIREN
MODULE)
1A, 50V DIODE**
IN 4001 07-001
(LOCATE AT SIREN)
FIRE
ALARM
INTRU-
SION
ALARM
REGENCY MODEL 4720(A)
PANEL TERMINALS
REGENCY
MODEL 4180
STATUS
DISPLAY
MODULE
CONNECTOR
AND
TERMINAL
SUPERVISED SIREN
MODULE TERMINALS
* OR ANY ZONE INPUT PROGRAMED AS A
NORMALLY-OPEN SUPERVISORY INPUT.
56
10
** NOTE POLARITY.
38