Model 4724 Control Expander Installation Manual (P/N 150596-02, Rev. A) Revised 8/98
41
NOTE
1
These zones will be displayed as AUXILIARY on the LCD. If LOCAL is selected, the panel
will not dial out.
2
12 (UNUSED) can be selected to create a zone that does not cause an alarm.
Do NOT select
14 or 15 as zone type. They are there to allow additional zone types to be made available in the
future.
3
Zone Type 6 was changed from “Gas” to “Supervisory with Revision J of the 4724-2 con-
trol software.
SIL ALM:NO
If you select this option, alarms activated by this panic key will be reported to the central sta-
tion, but no audible alarm will sound.
REP DLY:NO
If you select this option, alarms activated by this panic key will be reported after a pro-
grammed delay time. The delay time is programmed in Timers (Menu 11).
BELL DLY:NO
Select this option to create a delay between the time an alarm condition is sensed by a zone of
the specified type and the time the alarm bell is sounded.
NO SHUTD#1:NO
If this option is selected, the bell will not shut down until the panel is disarmed.
The display now advances to the next touchpad panic zone.
Table 11: Loop Response Times
Selection # Loop Response Time
0 0.01 seconds
1 0.06 seconds
2 1.0 second
3 10.0 seconds
Table 12: Zone Types
Selection # Zone Type Selection # Zone Type
0 HOLDUP 8
WATER
1
1FIRE 9
HEAT
1
2 EMERGENCY 10
COLD
1
3 PANIC 11
LOCAL
1
4 BURGLARY 12
UNUSED
1, 2
5 TAMPER 13
DOORBELL
1
6
GAS
3
14
UNUSED
1, 2
7
UNDEFINED
1
15
UNUSED
1, 2