53
9.3 Uploading Event Memory
1. When the Panel Interface Menu appears, select M to upload event memory from a particu-
lar account and save it on a disk at the central station.
2. Enter the account number when prompted to do so. The letter “E” will appear, followed by
the account number, on four different lines of the Up/Downloads column.
3. Initiate an upload, either by dialing the panel from the computer or by having someone
press 4 TEST on a touchpad at the account section
4. Select C to save the upload, then enter the account number to be saved.
NOTE Event information will be saved under a file name consisting of the account number with the
extension “.EVT” on the end.
NOTE The 4724's event memory is NOT cleared when the information is uploaded.
9.4 Programming Procedure
Figure 4 (located after Section 7.6 of this manual) is a diagram of 5540 menu structure. For
instructions on programming auxiliary device outputs using the 5540 software, see Section 9.5
of this manual.
9.4.1 Reprogramming the Options
1. When the Panel Interface Menu appears, press the A key to reprogram any of the options.
You will be prompted for an account number to edit.
2. On the Edit Account Menu, select the type of options you wish to program.
3. When you finish programming the options on one of these menus, press ESC to get back
to the Edit Account Menu, then choose another set of options to program.
4. After you have reprogrammed all the options, press ESC again. Then follow the screen
prompts to save and download the new data.
5. After you have entered the subscriber's phone number, the number will appear on the
screen, followed by “PRESS ESC TO TERMINATE, WAITING FOR ANSWER…
Several seconds will elapse before the call goes through and the screen indicates that
downloading is taking place.
9.4.2 Printing the Options
To print the data from a particular options menu, go to the menu and press the 0 key.
9.4.3 Verifying the Selections
To make sure the correct data has been downloaded to the subscriber's panel, you may wish to
have the panel send the data back so you can review it.
1. On the 4724 panel menu, select E, then follow the prompts to upload the data from the
4724 to your computer.
2. To view the uploaded data, select B on the 4724 panel menu.
3. To save the uploaded data, select C on the menu.
CAUTION! Before editing or modifying an upload, you must save it.