Page view 64
Regency
®
Model 4724 Control Expander Installation Manual (P/N 150596-02, Rev. A) Revised 8/98
57
2. 1 RLY[4].7 = AZONES[18].5
The output label RLY[4].7 refers to the eighth output (.7) on the second group of outputs
on the second 4180 module ( [4] ). The status label AZONES[18].5 refers to the armed
status of the sixth zone (.5) of the zone group to which [18] has been assigned (Zones 137
- 144)—in other words, Zone 142. Table 19, “Output Designations,” shows which zones
are assigned to each bracketed number.
3. 1 TER16 = (THR = 1) OR (THR = 2)
The output label TER16 refers to Terminal 16 of the 4720. (THR, = 1) refers to the hour
that begins at 1:00 AM and ends at 1:59 AM. (THR, = 2) refers to the hour that begins at
2:00 AM and ends at 2:59 AM. If the current time falls within either of these two intervals,
the LED connected to Terminal 16 will light. Because these two time periods happen to be
consecutive, the LED will remain on continuously from 1:00 AM to 2:59 AM; it will not
go off between the two time intervals.
Table 18: Programmable I/O Output Labels (Read/Write)
1
Label
2
Data Type Function
RLY [4] BITS 4180 Status Relays
TER16 BIT Output on Terminal 16
TER15 BIT Output on Terminal 15
TER18 BIT Output on Terminal 18
X10[4] BITS X-10 output bits
SCR[8]
NUMBER,
BITS
User scratch area
NOTE 1. An output can be generated (written-left side of if as a result) in inter-
nal condition or its own status can be read (right side of statement) to
generate an output on some other device.
2. In this column the number in brackets [ ] indicates how many devices
or components of this type available.
Table 19: Output Designations
Label Function
RLY[1] Outputs on 4180 Module 1, Connector P2
RLY[2] Outputs on 4180 Module 1, Connector P3
RL [3] Outputs on 4180 Module 2, Connector P2
RLY[4] Outputs on 4180 Module 2, Connector P3
RLY[1].0 Outputs on 4180 Module 2, Connector P2, Pin 8
RLY[1].1 Outputs on 4180 Module 2, Connector P2, Pin 7
RLY[1].7 Outputs on 4810 Module 1, Connector P2, Pin 1
RLY[2].0 Outputs on 4180 Module 1, Connector P3, Pin 8
RLY[2].1 Outputs on 4180 Module 1, Connector P3, Pin 7