Regency
®
Model 4724 Control Expander Installation Manual (P/N 150596-02, Rev. A) Revised 8/98
11
Section 7: Using the 4724 Built-In Programmer
The 4724 includes a built-in programmer that can program all system operating parameters.
The programmer is simple to use and includes help displays for entering data. The 4724's built-
in programmer can be accessed using any 4660 series touchpad. Figure 4 (Section 7.6 of this
manual) is a diagram of the built-in programmer's menu structure.
7.1 Entering Program Mode
To go into Program mode, press 1 1 TEST followed by a valid code.
Code 0 (installer's code) is granted access to all system options. Other codes are granted access
to 4 of the program areas if the PG, or “program” access, option is enabled for that code. When
Program mode is active, the display lists the available menus one by one.
NOTE The factory programmed value for Code 0 (the installer's code) is “1234.”
Press the number of the menu that includes the options you wish to program. Press the TEST
key. The first line of the touchpad display will show the option name and the most recently
programmed value for that option. The second line will show the available choices.
To exit the current menu, press the MUTE key once. To leave Program mode at any time, press
MUTE twice, until you no longer see the scrolling key prompts.
NOTE Do NOT follow the above procedure to program new secret codes for Code 0 and Code 1.
Instead, press 7 TEST (see Section 7.6 of this manual).
7.2 Stepping Through the Program
By pressing the TEST key, you can view the current option settings in a menu. The option
description appears on the top line, followed by the current setting. The bottom line shows
what keys can be used at that step of the program. In some cases, the key name will be fol-
lowed by a word that explains how the key is used.
Example:
“TEST-ENTER” means you use the TEST key as you would use the
ENTER key on a computer.
Press TEST again to proceed to the next option without changing the one you just viewed.
Some of the menus (Access, for example) repeat options for many numbered items. The first
step in the loop may allow you to choose what numbered item you wish to program. The menu
will automatically advance to the next numbered item when it reaches the end of the options
for the current item.
7.3 Programming the Options
For some options, the available choices are numbered and appear on the bottom line of the line
display.
1. To program an option, type in the number of the desired choice. The top line of the touch-
pad display will show the new value.
2. For yes/no options, Press 0 for NO and 1 for YES.
3. Press the TEST key. The display will advance to the next option.