Model 4724 Control Expander Installation Manual (P/N 150596-02, Rev. A) Revised 8/98
32
BELL DLY#1:NO
If this option is selected, there will be no bell output, unless the dialer fails.
NO SHUTDOWN#1:NO
If this option is selected, the bell will not shut down, until the panel is disarmed.
ZONE:#2
Select the next zone that you will program for options. The options will repeat for all 144
zones.
8.8 Accounts (Menu 7)
ACCOUNT:#1(1-4)
Select what account (1-4) you wish to reprogram.
PHONE NUMBER#1:
Enter Phone #1, up to 16-digits. Enter “A” (01) for a pause. Enter “D” (04) for a second dial
tone. Press 6 before each digit of the phone number. (See Section 8.5 of this manual for an
example.)
ACCT#1:000000
Enter the digits for the account number (six-digits maximum).
REP ALRM#1:YES
Select this option if you want alarms to be reported to Phone #1.
REP TRBL#1:YES
Select this option if you want trouble conditions to be reported to Phone #1.
REP BYPS#1:NO
Select this option if you want bypassed (shunted) zones to be reported to Phone #1.
REP RSTR#1
Select this option if you want restorals to be reported to Phone #1. Restores will report only to
the same numbers that the alarm or bypass reported to.
REP OPRST#1:NO (Report Open Reset, Phone #1)
Select this option if you want the system to report to Phone #1 when the system is disarmed
from an alarm condition. If you will select the next option (REP OP/CL#1) for Phone #1, you
must also select REP OPRST#1.
REP OP/CL#1:NO
Select this option if you want the system to send Normal Reports and Exceptional Open Until
Close Reports to Phone #1.
REP DOOR#1:YES
Select this option if you want door access information to be reported to Phone #1.