Model 4724 Control Expander Installation Manual (P/N 150596-02, Rev. A) Revised 8/98
33
REP TEST #1:YES
Select this option if you want test signals and event memory information to be reported to
Phone #1.
MUST REP#1:YES
If this option is selected, the system MUST report to Phone #1. If this option is not selected,
Phone #1 will only be used as a backup if an event cannot be reported to another number.
NOTE The Must Report Numbers must be the lower numbers (before the backups). Your choices are
1, 1&2, 1&2&3, 1&2&3&4.
FORMAT#1:SIA8
From Table 8, select the digit next to the format that Account #1 will use. The compatible
Regency receivers are also below.
NOTE A. SIA8 and SIA20 are the only formats that can report event memory and zone numbers
higher than 99.
B. Do not select SIA20 unless the receiver has a 9004I card. The 9004 card can only accept
SIA8 (formerly SEA8).
ATTEMPTS #1:1
Enter the number of attempts (1-15) that the communicator will try to report to this account
number before switching to the next number (typically one attempt).
LISTEN IN#1:0
Enter, in seconds, the length of time the central station can listen to the site on this account
number (20 - 255 seconds; 0 if not used).
Select this option to allow the central station to listen in to the site on this account number.
NOTE The Listen-in feature is not recognized by UL.
L ALM/TST#1:NO
Select this option to enable the listen-in function only with alarms and tests on this number.
Table 8: Reporting Formats
Selection Format Compatible Receiver
0 SIA8 9004, 9004I
1 FSK1 8520
2 FSK2 9002
3 BFSK 1400 Hz 9002
4 BFSK 2300 Hz 9002
5 SIA20 9004I
6 SK4+2 9002